CW SPECIFICATIONS MANUAL (M) PROGRAMMABLE (P)
Power Factor*
Range 0 to 1
Accuracy ±4% of range for linear loads
Resolution 0.01
Crest Factor*
Range 0 to 3.5
Accuracy ±5% of range
Resolution 0.01
FRONT PANEL
Displays & Indicators
Menu/Status Green LED for output on, V mode, I mode, slave Green LED for remote and lockout, voltage mode,
Red LED for fault current mode, red LED for fault
Enter/escape buttons are present for programming
Voltage 4 digit display, green LED (volts) 4 digit display, green LED (volts, watts, VA, PF, OVP)
Current/Frequency 4 digit display, green LED (amperes) 4 digit display, green LED (amps, Hz, Pk amps,
CF, I Limit)
Program/Measure Green LED (amps, Hz I Limit)
V Range High/Low Green LED
INPUT
Voltage and Frequency
CW 801 90 to 264 VAC, 47 to 63 Hz, single phase
CW 1251 103 to 264 VAC, 47 to 63 Hz, single phase
CW 2501 180 to 264 VAC, 47 to 63 Hz, single phase
Current
CW 801 13 ARMS max
CW 1251 18.5 ARMS max
CW 2501 19.5 ARMS max
Power Factor >0.99 typical at full load nominal line
Efficiency >73% typical at full load
GENERAL
Regulatory Compliance CE Mark, UL Listing Mark and C-UL Listing Mark (consult factory for availability)
Dimensions
CW 801 and CW 1251 2U 3.5" H (89 mm) x 19" W (483 mm) x 20.6 D (524 mm)
CW 2501 3U 5.25" H (133 mm) x 19" W (483 mm) x 20.6" D (524 mm)
Weight
CW 801 48 lbs (22 kg)
CW 1251 53 lbs (24 kg)
CW 2501 86 lbs (39 kg)
Shipping Weight
CW 801 56 lbs (25 kg)
CW 1251 61 lbs (28 kg)
CW 2501 94 lbs (43 kg)
Environmental
Cooling Dual speed fan with side air intake, exhaust to rear
Operating Temperature 0 to 40°C
Storage Temperature -40 to 70°C
Humidity 0 to 85% at 25°C derate to 50% at 40°C (non condensing)
Altitude Operating full power available up to 6,000 feet, non operating to 40,000 feet
* Note: In a parallel system (for programmable units only), the current/power displayed on the master unit is the sum of all units in the system.
Vista de página 4
1 2 3 4 5 6

Comentários a estes Manuais

Sem comentários